- Clear display and simple operation via LED displays and operating keys
- Basic version with 4 limit value groups for subscribers of the 05 series with up to 32 automatic detectors or 10 manual call points per detector group (max. 128 detection points)"
- 1 alarm and 1 fault relay
- 1 monitored siren output 450 mA
- 4 programmable OC outputs, 1 programmable input
- Two expansion slots for flexible system expansion to max. 12 limit value groups (384 detector points)
- Interface card for extinguishing area control available on request
- Interface card for hazardous areas available
- Relay and signaling lines expandable
- Direct connection of special detectors possible
- Integrated power supply according to EN 54-4: 1997/A1: 2006/A2: 2006
- Independent connection of the detector and alarm generator groups
- Individual programming via menu keys, e.g. alarm delay, fast mode, day/night mode
- 3 access level
- Integrated one-man revision mode
- Connection of parallel display panels for collective messages (optional)
Products fire alarm systems
Modular fire alarm panel 4/8/12 detector groups
Modular microprocessor-controlled fire alarm panel for connection of all components of the 05 series. Approved according to EN 54-2: 1997/A1: 2006, EN 54-4: 1997/A1: 2006/A2: 2006 and EN 12094-1
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 230 V AC, 50/60 Hz |
Emergency Supply | 2x 12 V DC / 7,2 Ah |
Alarm Current | 1 A |
Operating Temperature | 0°C - 50°C |
Dimensions (H x W x D) | 300 x 370 x 118 mm |
Weight | 2 Kg (without batteries) |
Material | ABS |
Color | white |
Standards | EN 54-2, EN 54-4, |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .