Products fire alarm systems

Product Image

Modular fire alarm panel 4/8/12 detector groups

Modular microprocessor-controlled fire alarm panel for connection of all components of the 05 series. Approved according to EN 54-2: 1997/A1: 2006, EN 54-4: 1997/A1: 2006/A2: 2006 and EN 12094-1

Art-Nr.: 40030 | ALPHA 4/8/12

documents

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .

Product Information

  • Clear display and simple operation via LED displays and operating keys
  • Basic version with 4 limit value groups for subscribers of the 05 series with up to 32 automatic detectors or 10 manual call points per detector group (max. 128 detection points)"
  • 1 alarm and 1 fault relay
  • 1 monitored siren output 450 mA
  • 4 programmable OC outputs, 1 programmable input
  • Two expansion slots for flexible system expansion to max. 12 limit value groups (384 detector points)
  • Interface card for extinguishing area control available on request
  • Interface card for hazardous areas available
  • Relay and signaling lines expandable
  • Direct connection of special detectors possible
  • Integrated power supply according to EN 54-4: 1997/A1: 2006/A2: 2006
  • Independent connection of the detector and alarm generator groups
  • Individual programming via menu keys, e.g. alarm delay, fast mode, day/night mode
  • 3 access level
  • Integrated one-man revision mode
  • Connection of parallel display panels for collective messages (optional)

Technical Specifications

Supply Voltage 230 V AC, 50/60 Hz
Emergency Supply 2x 12 V DC / 7,2 Ah
Alarm Current 1 A
Operating Temperature 0°C - 50°C
Dimensions (H x W x D) 300 x 370 x 118 mm
Weight 2 Kg (without batteries)
Material ABS
Color white
Standards EN 54-2, EN 54-4,

Certificates / Approvals

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .