- Activation, monitoring and supply via Loop 3000-protocol
- Integrated automatic reset function at signal "external signal line on/off" by the fire control panel
- Monitoring of the operating status via Loop 3000
- Independent programming via loop address
- Automatic and manual addressing with Loop 3000
- Integrated Isolator
- 28 different tones, adjustable via DIP-switch including DIN-signal
- Loudness adjustable via DIP-switch
- Functions completely integrated via Loop 3000-protocol
- Aesthetical, robust wall mounted housing according with IP 41
- Integrated detector base of the PL 3000 series
Products fire alarm systems
CONUS - Loop sounder -MLAR - white
Intelligent acoustic signaling device for the loop3000 for the acoustic alarm with bidirectional isolator according to EN 54-3 and EN 54-17 with MLAR function.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 18 V to 32 V DC (max. 34 V DC) |
Quiescent Current | 400 µA |
Alarm Current | 6 mA |
Ambient Temperature | -10°C to +60°C |
Storage Temperature | -25°C to +70°C |
Humidity | max. 95% |
Protection Class | IP 41 |
Weight | 285 g |
Material | ABS |
Standards | EN 54-3 and EN 54-17:2005 |
Remarks | For the planning of the quantity of Loop 3000-signaling devices please use the Loop calculator tool. |
Dimensions (H x D) | 66 mm x 145 mm |
Volume control | In 4 steps |
Loudness | Up to 95 dB(A) @ 1 m |
VdS-Approval | G 213054 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the