- Activation, monitoring and supply via Loop 3000-protocol
- Integrated automatic reset function at signal "external signal line on/off" by the fire control panel
- Monitoring of the operating status via Loop 3000
- Independent programming via loop address
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Integrated 1 Hz LED-beacon
- Functions completely integrated via Loop 3000-protocol
- Aestethical robust wall mounted housing according with IP 43
- Not usable as signall device according to EN 54-23
Products fire alarm systems
Loop Flasher - red
Intelligent optical signaling device for the Loop 3000 for the external alarm with bidirectional isolator according to EN 54-17. Wall mounted housing.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 30 V DC (2-wire bus) |
Quiescent Current | 400 µA |
Alarm Current | 6 mA |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 43 |
Weight | 145 g |
Material | ABS, Glass |
Color | White |
Dimensions (H x D) | 80 mm x 98 mm |