- Monitoring of the operating statuses via the Loop 3000
- 2 monitored inputs to be switched very rapidly (resistance at rest 3.3 k Ohm, triggering 680 Ohm in parallel)
- 1 monostable, potentialfree output for fail safe controls
- Integrated bi-directional isolator
- LED service display for alarm (red), fault and sign of life indication (yellow) attached to the housing.
- Robust,weatherproof, halogen-free, impact resistant housing according to DIN EN 60670 (VDE 0606)
Products fire alarm systems
Fail Safe Ansteuermodul
Intelligent fail-safe control module for the Loop 3000 with an integrated bi-directional isolator for the triggering of technical facilities which necessarily require a fail-safe control. The output is switched off by triggering at the module, fire contro
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 17 V to 32 V DC (abs. max. 34 V DC), 2-wire-Bus |
Quiescent Current | ca. 460 µA |
Alarm Current | 6 mA / 9,5 mA (add. red LED) |
Operating Temperature | -20°C to +60°C |
Storage Temperature | -25°C to +85°C |
Protection Class | IP 54 |
Dimensions (H x W x D) | 93 mm x 93 mm x 55 mm |
Weight | 115 g |
Material | Polycarbonate, membrane made of TPE |
Color | Grey |
Standards | DIN EN 54-17 ; DIN EN 54-18 |
Remarks | No operation in stab modus allowed. |
Switched output | 1 Optorelay, potentialfree, monostable, fail safe, 30V DC / max. 1A |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .