- Connecting module with one freely programmable input and one freely programmable output
- Additional parallel alarm output (blinking) for the control of a status indicator (without series resistor)
- Programmiermöglichkeit für unterschiedliche Schaltvarianten des Ein- und Ausgangs, auch mit Zeitsteuerung
- Monitoring of the operating status via Loop 3000
- Independent programming of input and output
- Automatic and manual addressing with Loop 3000
- Integrated Isolator
- Completely encapsulated module for the integration in special applications with control by the Loop 3000
- Functions completely integrated via Loop 3000-protocol
- For VdS-conform installation in housing Mini 25L (part-no. 53372)
Products fire alarm systems
In-/Output module mini
Intelligent Input / Output module mini for the Loop 3000 with bidirectional isolator for the integration in special detectors and externally connected modules according to EN 54-18. Including one monitored input and one open collector output
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V DC on to 2-wire bus (max. 34 V DC) |
Quiescent Current | 380 µA |
Alarm Current | 380 µA; 5 mA with activated LED |
Output | Open collector 500 mA, 30 V DC |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 30 |
Dimensions (H x W x D) | 27 mm x 73 mm x 15 mm |
Weight | 20 g |
Material | ABS |
Color | black |
Standards | DIN EN 54-18, EN 54-17 |
DIN EN | 54-17, 54-18 |
VdS-Approval | G 206047 |