- Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm for the fire detection
- Individual change of detector class for sensitivity levels 1 to 6 using DPT
- Pollution detection of the smoke measurement chamber by an additional optical path
- Detector sensitivities automatically adapted and programmable
- Intelligent analysis and suppression mode for the elimination of false alarms
- Fault monitoring of the measurement chamber signal and D-Loop electronics
- Periodic sensor test
- Automatic and manual addressing on D-Loop
- Integrated isolator
- Freely programmable alarm output to control parallel indicator
- Functions completely integrated via D-Loop protocol
- Day-/Nightmode with selectable sensitivities
- Integrated event log
- Multicolour LED for alarm (red) and fault (yellow)
- LED blinking option for life signal or maintenance mode
- Delivery including dust protection cover for installation phases
Products fire alarm systems
Intelligent multi criteria detector with isolator
Intelligent multi sensor detector for D - Loop with heat and two optical sensors and a bidirectional isolator according to EN 54-17/-18/-29
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 30 V to 41 V DC on 2-wire bus (nom. 40 V DC) |
Quiescent Current | 180 µA |
Alarm Current | 5 mA |
Output | optional relay 0,4 A/ <30 V DC |
Ambient Temperature | -10°C to +65°C |
Humidity | max. 93 % |
Protection Class | IP 20 B |
Weight | 150 g including base |
Material | ABS |
Color | Housing white (similar to RAL 9003) |
Standards | EN 54-17, EN 54-18, EN 54-29 |
Dimensions (H x D) | 62,6 x 104 mm |
Response Sensitivity | Adjustable in 6 sensitivity levels |