- Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel
- Connecting module with one freely programmable input and one output for the connection of signalling devices
- Input for connecting an external 24 V DC power source to supply the signaling line
- Programming of different switching variants of input and output also with time control
- Independent programming of input and output
- Monitoring of the operating status via D-Loop
- Automatic and manual addressing with D-Loop
- Integrated isolator
- Functions completely integrated via D-Loop protocol
- 2 red LED for status information input and output, 1 yellow LED for fault indication
- Robust wall mounted housing
Products fire alarm systems
In-/Output module for signaling devices 1x
Intelligent Input/Output module for the D-Loop for the control of external optical and acoustic signaling devices with bidirectional isolator according to EN 54-17 and EN 54-18. Including one monitored fault input and one monitored voltage output for signalling devices.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 30 V to 41 V DC on 2-wire bus (nom. 40 V DC) |
Quiescent Current | 150 µA |
Alarm Current | 1 mA |
Output | max. 1,5 A / 24 V DC |
Ambient Temperature | -30°C bis +70°C |
Storage Temperature | -10°C to +50°C |
Humidity | max. 93 % |
Protection Class | IP 43 (IP 54 with PG11 cable glands - not included in the delivery) |
Dimensions (H x W x D) | 170 x 120 x 70 mm (without cable glands) |
Weight | 400 g |
Material | ABS/PC |
Color | Housing grey |
Standards | EN 54-17, EN 54-18 |
Inputs | 420 µA / 24 V DC |
VdS-Approval | G 219044 |