- Connecting module with one programmable input and one programmable output
- Programming of different switching variants of input and output also with time control for one detector group
- Independent programming of input and output
- Monitoring of the operating status via D-Loop
- Automatic and manual addressing with D-Loop
- Integrated isolator
- Functions completely integrated via D-Loop protocol
- 2 red LED for status information input and output, 1 yellow LED for fault indication
- Housing for DIN rail mounting
Products fire alarm systems
In-/Output module 1x DIN-rail
Intelligent Input/Output module for the D-Loop in DIN-rail version with bidirectional isolator according to EN 54-18 and EN 54-17. With one monitored input and one potential free relay output
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 30 V to 41 V DC on 2-wire bus (nom. 40 V DC) |
Quiescent Current | 150 µA |
Alarm Current | 1 mA |
Output | Relay 2 A / 30V DC |
Ambient Temperature | -30°C to +70°C |
Storage Temperature | +10°C to +50°C |
Humidity | max. 93 % |
Protection Class | IP 20 |
Dimensions (H x W x D) | 108 x 112 x 32,5 mm |
Weight | 100 g |
Material | PA6 |
Color | Green |
Standards | EN 54-17, EN 54-18 |
Remarks | Compatible with balanced 7.5 mm and 15 mm rails. Locking adapters are required on both sides for a secure hold on DIN rails (not included in the scope of delivery). |
Inputs | Potential free contact (selectable monitored) |
VdS-Approval | G 219038 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .