- Connection to the ALPHA 4/8/12 fire alarm panel via an EX barrier SBEx BZ1
- By using 2 sensors that react to different infrared wavelengths, fires caused by highly flammable liquids or gases can be detected quickly and reliably
- Suitable for zone 0""
Products fire alarm systems
IR flame detector EX version, limit value
Conventional Intrinsically safe infrared flame detector for use in potentially explosive atmospheres (ATEX)
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 9 V DC - 28 V DC |
Quiescent Current | < 515 µA |
Alarm Current | 32 mA |
Operating Temperature | -10°C to +55°C |
Storage Temperature | +10°C to +50°C |
Humidity | 93% |
Protection Class | IP 20 |
Weight | 125 g with base |
Material | ABS, antistatic |
Color | white |
Standards | EN 54-10, EN 50014 (1997) with Annex 1 und 2, EN 50020 (2002), EN 50284 (1999) |
Dimensions (H x D) | 41 x 104 mm (diameter) |
Sensortyp | 2x infrared |
Surveillance Area | Depending on the distance conical 35-45° related to the visual axis |
Surveillance Distance | According to EN 54-10: Class 1 up to 25 m, Class 2 up to 17 m (factory setting) and Class 3 up to 12 m |
Rated Voltage | 20 V DC |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .