- Integrated professional temperature measurement system with highest safety for safe alarm verification
- Reliable detection of static or dynamically increasing temperature values
- ATEX version for use in intrinsically safe environments
- Especially suitable for average ambient temperatures below +10° C
- Static response temperature +60°C (+/- 3°)
- Dynamic response temperature > 9°C / min
- Alarm output for controlling a detector parallel display
- Alarm indicator with red LED
- Removal lock
- Suitable for detector base series 05eX
Products fire alarm systems
Thermal detector Atex
Conventional Intrinsically safe thermal detector for early fire detection and signalling, with thermal measuring method according to EN 54-5 (class A1R) for use in hazardous areas (ATEX)
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 10 V DC - 28 V DC |
Quiescent Current | < 150 µA |
Alarm Current | 24 mA (+/- 2 mA) |
Output | 0 V in idle state / 3.3 V DC on alarm |
Operating Temperature | -20°C to +55°C |
Storage Temperature | +10°C to +50°C |
Humidity | 93% |
Protection Class | IP 32 |
Weight | 130 g |
Material | ABS |
Color | white |
Standards | EN 54-5 (Class A1R) |
Remarks | S05Ex detector base must be ordered separately |
Dimensions (H x D) | 56 x 104 mm (diameter) |
Sensortyp | Thermal |
Rated Voltage | 20 V DC |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .