Products fire alarm systems

Product Image

IR flame detector, limit

Conventional Infrared flame detector

Art-Nr.: 40164 | IRY2 + S95

documents

    No documents.

Product Information

  • Connection to the ALPHA 4/8/12 fire alarm panel
  • By using 2 sensors that react to different infrared wavelengths, fires caused by highly flammable liquids or gases can be detected quickly and reliably
  • OC output for detector parallel display limited to 24 mA / 24V DC

Technical Specifications

Supply Voltage 15 V DC to 28 V DC
Quiescent Current < 515 µA
Alarm Current 32 mA
Operating Temperature -10°C to +55°C
Storage Temperature +10°C to +50°C
Humidity 0,95
Protection Class IP 20
Weight 125 g with base
Material ABS
Color white
Standards EN 54-10
Dimensions (H x D) 42 x 104 mm (diameter)
Sensortyp 2x infrared
Surveillance Area Depending on the distance conical 35-45° related to the visual axis
Surveillance Distance According to EN 54-10: Class 1 up to 25 m, Class 2 up to 17 m (factory setting) and Class 3 up to 12 m
Rated Voltage 20 V DC

Certificates / Approvals