- Up to 126 Sounder-Flasher at 3,000 meters loop length with maximum volume
- 100% uninterruptible loop alarm (zero seconds according to MLAR requirement)
- Cost reduction, the integrated battery enables decentralised energy management, therefore no additional fire protection housing for the BMZ is required
- Full integration into Loop3000 topology (with DC3500 from V5.0.4)
- Individual configuration via DPT (41 tones incl. DIN tone, 4 different alarm scenarios, 4 volume levels)
- Optimized, homogeneous SPL dispersion
- Integrated automatic reset function for signal "external signal transmitters on/off" of the fire alarm control panel
- Monitoring of the operating status via Loop3000
- Visual Alarm Device according to EN 54-23, red LEDs
- 3 Brightness levels
- Flashrate 1 Hz or 0,5 Hz
- High: C-3-6; W-2,4-3
- Medium: C-3-5; W-2,4-2,8
- Low: C3-4; W-2,4-2,3
- Optional automatic or manual addressing.
- Integrated bidirectional isolator according to EN 54-17
- Easy installation, the base allows quick pre-installation and loop connection
- Designed for wall and ceiling mounting (cover cap available as accessory)
- Integrated base for Loop3000 series automatic detectors (ceiling mounted)
- Long-term investment through physical separation of signalling and fire detection. The sounder can continue to be used if it is necessary to replace the detector.
- Service-friendly due to integrated battery monitoring and runtime prognosis via DPT
- Esthetic, robust housing according to IP 41
Products fire alarm systems
CONUS II Sounder-Flasher Loop3000, red housing, red flash
Loop controlled multi-tone sounder-flasher for an acoustic alarm according to EN 54-3 and a visual alarm according to EN 54-23
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V (abs. max. 34V) |
Quiescent Current | < 500 µA |
Alarm Current | Powered by battery |
Operating Temperature | -10°C to + 55°C |
Storage Temperature | -20°C to + 65°C |
Humidity | Max. 93% (non condensing) |
Protection Class | IP 41 |
Dimensions (H x W x D) | 80 mm x 145 mm x 145 mm |
Weight | 428g |
Material | ABS |
Standards | EN 54-3 EN 54-23 |
Remarks | Accessories: Cover cap for PL 3300r CONUS S/SF with cable, red (packaging unit 10 pcs.). For use without smoke detector attached to PL 3300r CONUS S/SF, part no. 33692 Accessories: Mounting base, for PL 3300r CONUS S/SF red, part no. 33694 |
Flash frequency | 1 Hz/0,5 Hz |
Loudness | 94 dB @ 1m, DIN 33404, Part 3 |
Rated Voltage | 32 V |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the