- Primary pulsed mains adapter with electronical overload function
- Integrated deep discharge protection (end-of-discharge voltage at discharge current = 21.0 V DC at 0.1 x battery capacity)
- Controlled output voltage 24 V DC
- Intelligent battery management
- Status LEDs for operation, fault (including display of the error type)
- Protection against electric shock (personal protection) with additional plastic protection cover caps
Products fire alarm systems
Primary pulsed power supply, 3 A, metal
Universal primary pulsed mains adapter for the use as an emergency power supply unit to supply 24 V DC with 3 A.
The device combines several functions: energy supply, battery charger and battery monitoring and meets all requirements of EN 54-4 + A1 + A2.
The power supply conforms to (EU) No. 305/2011 - Construction Products Regulation, the 2014/35 / EU - Low Voltage Directive and the 2014/30 / EU - EMC Directive.
In addition, it meets also the requirements of EN 50131-6 (type A, up to grade 4, environmental class II, additional sabotage protection required).
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 230 V AC / 50 Hz |
Output | Potential-free relay output for general fault with a switching capacity of 1 A at 30 V DC |
Ambient Temperature | -5°C to +40°C |
Humidity | max. 95 % (not condensing) |
Protection Class | IP 30 |
Dimensions (H x W x D) | 404 mm x 404 mm x 110 mm |
Weight | 5 kg without batteries |
Material | Metal (enclosure and door) |
Color | RAL 7035 light-grey with surface structure |
Output Current | 3 A depending on operation mode |
Battery capacity | 7 Ah to 17 Ah |
DIN EN | EN 54-4, EN 50131-6 |