- Clear display and easy operation via high resolution colour display with capacitive touch screen
- USB-Interface for easy programming via DPT-Software
- Space for up to 15 modules to connect up to 126 Loop 3000 fire detection system components per module
- Programming of up to 1890 detector zones
- Event log memory for 100.000 messages
- Easy programming of up to 10.000 cause and effects
Products fire alarm systems
Fire control panel dc3500 ML
Compact microprocessor controlled fire control panel for the use with the Loop 3000 fire detection system components.
Language kit need to be ordered separately. Please be aware there are two different kind of language kits, one for the 4,3" HMI and one for the 7" HMI.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 90-265 V; 50-60 Hz |
Emergency Supply | 2 x 12 VDC /17 Ah, 26 Ah, 45 Ah |
Quiescent Current | 280 mA |
Alarm Current | 360 mA depending on extention |
Output | 1 x 24 VDC / 800 mA monitored for alarming devices. 2 relay outputs for alarm and fault, 4 relay outputs free programmable (30 VDC, 2 A / 125 VAC, 0,5 A) |
Ambient Temperature | -5°C to +40°C |
Humidity | 5% to 95% (not condensing) |
Protection Class | IP 30 |
Dimensions (H x W x D) | 600 mm x 450 mm x 240 mm |
Weight | 17,7 kg without batteries |
Material | Sheet metal |
Color | RAL 9006 |
Standards | EN 54-2: 1997 A1: 2006; EN 54-4: 1997 A2: 2006 |
Remarks | Standard includes the licence up to 250 participants |
Inputs | 2 potential free programmable inputs |
Display | 24-Bit-colour display 1024 x 600 pixel, LED-backlit. 23 fixed and 5 free programmable status indicators |
Power Supply | Pmax: 166 W |
Interfaces | USB-slave |
VdS-Approval | G 214222 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .