- Analysis of the optical spectrum ultraviolet light
- Robust housing for rough industrial environments
- High reliability against false alarms e.g. flashes or strong sunlight
- High sensitivity to fires
- Monitoring range up to 50m, monitoring area up to 676 m²
- Configuration for different applications via DIP-switch
- Monitoring of the optical windows against contamination (UV-range)
- Test of functionality and analysis of the measurement values via micro controller; faults can be displayed on the detector or on a seperate zone
- LED display red for alarm and yellow for fault
- Recommended cable: IY (St) Y 2x2x0, 8 mm
- Maintenance interface and event memory included
- Ground plate and mount included
- Connection via 1x IOM with the additional relay module - item no. 32928
Products fire alarm systems
UV flame detector
Conventional UV-flame detector for the protection against open flames (e.g. fire with gas, oil plastic and metal).
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 7,6 V to 30 V DC |
Quiescent Current | appr. 0,25 mA |
Ambient Temperature | -20°C to +80°C |
Protection Class | IP 67 |
Weight | 0,8 kg |
Material | Housing: Aluminum-die cast |
Standards | EN 54-10; Cl. 1 |
Remarks | Delivery includes Ground plate and mounting kit |
Dimensions (H x D) | 50 mm x 100 mm |
Surveillance Area | up to 676 m² |
Surveillance Distance | up to 50 m |
DIN EN | 54-10; Kl. 1 |
VdS-Approval | G 206132 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .