- Individual use of the thermal measurement according EN 54-5 in the sensitivity levels 2 to 5 as maximum detector (static --> A1S, A2S) or as rate-of-rise detector with maximum threshold (differential and static --> A1R, A2R)
- Individual change of detector class for sensitivity levels 2 to 5 using Easy Check 3000
- Pollution detection of the smoke measurement chamber by an additional optical path
- Detector sensitivities automatically adapted and programmable
- Integrated measurement-system and algorithm for condensation recognition (Humitec®)
- Intelligent analysis and suppression mode for the elimination of false alarms (e.g. cigarette smoke)
- Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm for the fire detection
- Fault monitoring of the measurement chamber signal and Loop 3000 electronics
- Periodic sensor test
- Automatic and manual addressing on Loop 3000
- Integrated isolator and T-branch option
- Alarm output to control parallel indicator
- Functions completely integrated via Loop 3000 protocol
- Presence and absence switching with selectable sensitivities
- Storage of last maintenance date
- Multicolour LED for alarm (red) and fault (yellow)
- Delivery including dust protection cover for installation phases
Products fire alarm systems
![Product Image](/typo3temp/assets/_processed_/3/4/csm_PICP_32149_603e20f702.jpg)
Intelligent multi sensor detector with isolator
Intelligent optical and thermal multi sensor detector for loop3000 with two optical and two thermal sensors and a bidirectional isolator for earliest fire detection and indication in all environments with difficult ambient conditions, according to EN 54-5
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V DC on 2-wire bus (max. 34 V DC) |
Quiescent Current | 320 µA |
Alarm Current | 5 mA |
Output | OC: max. 10 mA for parallel indicator or buzzer |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 40 |
Weight | appr. 80 g |
Material | ABS |
Color | Housing white (similar to RAL 9003) |
Standards | EN 54-5, EN 54-7, EN 54-17, prEN 54-29 |
Dimensions (H x D) | appr. 52 mm x 97 mm (with |
Response Sensitivity | Adjustable in 5 sensitivity levels |
DIN EN | 54-5 Kl. A1, 54-7, 54-17 |
VdS-Approval | G 208095 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .