Products fire alarm systems

Product Image

Laser smoke aspiration system Micra 25

Intelligent active Laser - smoke aspiration detector for earliest detection of fires in sensitive and extreme contaminated areas e.g. EDP-control room, hospital operating room, storage area, incineration plant, etc.

Art-Nr.: 31118 | Micra 25

documents

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .

Product Information

  • Integrated automatic adjustment of the detector to the ambient conditions via intelligent teach in modes
  • Intelligent laser sensor technology with consideration of ambient conditions for fast detection in difficult environments
  • Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm for the fire detection
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3, Laser dust discrimination and elimination system
  • Automatic day-/night mode for the adjustment from and to temporally different ambient conditions
  • Integrated fast learn for the automatic configuration of the system
  • Special integrated technology for the elimination of influences by pollution (dust etc.)
  • Integrated dust filter
  • 1 sampling pipe
  • Total pipe length 50 m up to 10 sampling holes
  • (25 m at highest sensitivity)
  • 1 recirculation pipe for the compensation of the intrasystem pressure gradient
  • Integrated RS 485-interface for the network of up to 127 participants
  • External voltage supply required
  • Connection to the Loop 3000 via IOM
  • Including mounting base and connection flange for the recirculation pipe

Technical Specifications

Supply Voltage 21,6 V to 26,4 V DC externally
Ambient Temperature -10°C to +60°C
Humidity max. 90% (not condensing)
Protection Class IP 50
Dimensions (H x W x D) 175 mm x 135 mm x 83 mm
Weight 1,01 kg
Material Cast aluminum, ABS
Color Housing light grey
Standards DIN EN 54-20
Remarks Accessories: relay board (part-no. 32236) with 5 potential free relay outputs, 4 for „alarm“ 1 for „fault“<br>Mnufacturer Kidde Products ( Stratos-Micra Aspirating Smoke Detector for use in fire detection and alarm systems)
Response Sensitivity Adjustable from 0,03 to 25% obs/m
Current Consumption 250 mA to 24 V DC
Particle sensitivity 0,0003 µm to 10 µm
DIN EN 54-20
VdS-Approval G 207078

Certificates / Approvals

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the