Product Information

  • Integrated LC-Display with 2 x 16 characters, arrow keys control panel
  • Integrated automatic adjustment of the detector to the ambient conditions via intelligent teach in modes
  • Intelligent laser sensor technology with consideration of ambient conditions for fast detection in difficult environments
  • Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm for the fire detection
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3, Laser dust discrimination and elimination system
  • Automatic day-/night mode for the adjustment from and to temporally different ambient conditions
  • Integrated fast learn for the automatic configuration of the system
  • Special integrated technology for the elimination of influences by pollution (dust etc.)
  • Integrated dust filter
  • 4 sampling pipes, up to 250 m maxium length:
  • Total pipe lenght 200 m up to 100 sampling holes
  • Maximum amount of holes according to EN 54-20 Class C : 80, Class B: 60, Class A: 20
  • 1 recirculation pipe for the compensation of the intrasystem pressure gradient
  • Integrated RS 485-interface for the network of up to 127 participants
  • Integrated potential free relays outputs for alarm and fault
  • External voltage supply required
  • Connection to the Loop 3000 via IOM

Technical Specifications

Supply Voltage 21,6 V to 26,4 V DC externally
Output 5 potential free relays for info, pre-alarm, fire 1, fire 2, fault
Ambient Temperature -10°C to +60°C
Humidity max. 90% (not condensing)
Protection Class IP 50
Dimensions (H x W x D) 372 mm x 427 mm x 95 mm
Weight 5,2 kg
Material Cast aluminum, ABS
Color Housing light grey
Standards DIN EN 54-20
Remarks Manufacturer Kidde Products (Stratos-HSSD 2 + Command Module Aspirating smoke detector for use in fire detection and alarm systems)
Response Sensitivity Adjustable from 0,002 to 25% obs/m
Current Consumption 450 mA at 24 V DC
Particle sensitivity 0,0003 µm to 10 µm
Pipe diameter 3/4"
DIN EN 54-20
VdS-Approval G 203024