- Exact pollution recognition by an additional independent measuring chamber
- Detector sensitivities automatically calibrated and freely programmable
- Fault monitoring of the measurement chamber signal and Loop 3000-electronics
- Periodic sensor test
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Alarm output to control parallel indicator
- Functions completely integrated via Loop 3000-protocol
- Presence and absence switching with freely selectable sensitivities
- Storage of last maintenance date
- Multicolour LED for alarm (red) and fault (yellow)
Products fire alarm systems
Optical smoke detector with isolator, Design 01-black
Optical smoke detector for Loop 3000 with 2 optical sensors for earliest fire detection and indication and with bidirectional isolator according to EN 54-7 and EN 54-17
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V DC on to 2-wire bus (max. 34 V DC) |
Quiescent Current | 280 µA |
Alarm Current | 5 mA |
Output | OC: max. 10 mA for parallel indicator or buzzer |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 40 |
Material | Metal cover, ABS |
Standards | DIN EN 54-7, EN 54-17 |
Color variant | black |
Dimensions (H x D) | appr. 47 mm x 110 mm |
Response Sensitivity | Adjustable in 5 sensitivity levels |
DIN EN | 54-7, 54-17 |
VdS-Approval | G 205046 |