- Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel
- Connecting module with one freely programmable fault input and one output for the connection of signalling devices
- Programming of different switching variants of input and output also with time control
- Monitoring of the operating status via Loop 3000
- Independent programming of input and output
- Automatic and manual addressing on Loop 3000
- Integrated isolator and T-branch option
- Functions completely integrated via Loop 3000-protocol
- Multicolour LED for alarm (red) and fault (yellow)
- Robust wall mounted housing according with IP 54
Products fire alarm systems
Output module for signaling devices 1x
Intelligent Input/Output module for the Loop 3000 for the control of external optical and acoustic signaling devices with bidirectional isolator according to EN 54-17 and EN 54-18. Including one monitored fault input and one potential free relay output fo
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V DC on 2-wire bus (max. 34 V DC) |
Quiescent Current | 460 µA |
Alarm Current | 460 µA; 5 mA with activated LED |
Output | 1 relay, 1 switchover contact 30 V DC/1 A |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 54 |
Dimensions (H x W x D) | 93 mm x 93 mm x 55 mm |
Weight | appr. 185 g |
Material | ABS |
Color | Housing white |
Standards | EN 54-18, EN 54-17 |
Remarks | Accessories: With UBW 3311 1A, part no. 33542, one monitored output can be realised |
DIN EN | 54-18, 54-17 |
VdS-Approval | G 205029 |