Products fire alarm systems

Product Image

Output module for signaling devices 1x

Intelligent Input/Output module for the Loop 3000 for the control of external optical and acoustic signaling devices with bidirectional isolator according to EN 54-17 and EN 54-18. Including one monitored fault input and one potential free relay output fo

Art-Nr.: 30211 | OMS 3301

documents

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .

Product Information

  • Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel
  • Connecting module with one freely programmable fault input and one output for the connection of signalling devices
  • Programming of different switching variants of input and output also with time control
  • Monitoring of the operating status via Loop 3000
  • Independent programming of input and output
  • Automatic and manual addressing on Loop 3000
  • Integrated isolator and T-branch option
  • Functions completely integrated via Loop 3000-protocol
  • Multicolour LED for alarm (red) and fault (yellow)
  • Robust wall mounted housing according with IP 54

Technical Specifications

Supply Voltage 15 V to 32 V DC on 2-wire bus (max. 34 V DC)
Quiescent Current 460 µA
Alarm Current 460 µA; 5 mA with activated LED
Output 1 relay, 1 switchover contact 30 V DC/1 A
Ambient Temperature -10°C to +60°C
Humidity max. 95%
Protection Class IP 54
Dimensions (H x W x D) 93 mm x 93 mm x 55 mm
Weight appr. 185 g
Material ABS
Color Housing white
Standards EN 54-18, EN 54-17
Remarks Accessories: With UBW 3311 1A, part no. 33542, one monitored output can be realised
DIN EN 54-18, 54-17
VdS-Approval G 205029

Certificates / Approvals

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .