- Voltage selection for the detector zone supply via "jumper" on the module board
- External supply of conventional detector zones for the flexible use of different conventional detectors with different current consumptions and operation voltages
- Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Functions completely integrated via Loop 3000-protocol
- Multicolour LED for alarm (red) and fault (yellow)
- Aestethical robust wall mounted housing according with IP 54
Products fire alarm systems
Conventional zone module
Intelligent Input module for the connection of one conventional detector zone to the Loop 3000 with bidirectional isolator according to EN 54-18. For the connection of conventional detectors with 12 V or 24 V technology.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V bis 32 V DC (abs. max. 34 V DC) auf 2-Drahtbus |
Quiescent Current | 560 µA |
Alarm Current | 560 µA; 5 mA with activated alarm-LED |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 54 |
Dimensions (H x W x D) | 93 mm x 93 mm x 55 mm |
Weight | appr. 190 g |
Material | ABS |
Color | Light grey (similar to RAL 7035) |
Standards | DIN EN 54-18, EN 54-17 |
DIN EN | 54-17, 54-18 |
VdS-Approval | G 206048 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .