- Connecting module with two programmable inputs and two programmable outputs
- Programming of different switching variants of input and output also with time control for one detector group.
- Monitoring of the operating status via Loop 3000
- Independent programming of input and output
- Automatic and manual addressing on Loop 3000
- Integrated isolator and T-branch option
- Functions completely integrated via Loop 3000-protocol
- Multicolour LED for alarm (red) and fault (yellow)
- Robust wall mounted housing according to IP 54
Products fire alarm systems
In-/Output module 2x
Intelligent Input/Output module for the Loop 3000 with bidirectional isolator according to EN 54-18 and EN 54-17. With two monitored inputs and two potential free relay outputs
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V DC on 2-wire bus (max. 34 V DC) |
Quiescent Current | 760 µA |
Alarm Current | 760 µA; 5 mA with LED active |
Output | 2 relays, 1 switchover contact 30 V DC/1 A each |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 54 |
Dimensions (H x W x D) | 93 mm x 93 mm x 55 mm |
Weight | appr. 190 g |
Material | ABS |
Color | Housing white |
Standards | EN 54-17, EN 54-18 |
Remarks | Accessories: With UBW 3311 1A, part no. 33542, one monitored output can be realised |
DIN EN | 54-17, 54-18 |
VdS-Approval | G 205029 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .