- Pollution detection of the smoke measurement chamber by an additional optical path
- Detector sensitivities automatically adapted and programmable
- Fault monitoring of the measurement chamber signal and Loop 3000 electronics
- Periodic sensor test
- Automatic and manual addressing on Loop 3000
- Integrated isolator and T-branch option
- Alarm output to control parallel indicator
- Functions completely integrated via Loop 3000 protocol
- Presence and absence switching with selectable sensitivities
- Storage of last maintenance date
- Multicolour LED for alarm (red) and fault (yellow)
- Delivery including protective cover for installation phase
Products fire alarm systems
Optical smoke detector with isolator
Optical smoke detector for Loop 3000 with two optical sensors for earliest fire detection and indication and with bidirectional isolator according to EN 54-7 and EN 54-17
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 15 V to 32 V DC on 2-wire bus (max. 34 V DC) |
Quiescent Current | 280 µA |
Alarm Current | 5 mA |
Output | OC: max. 10 mA for parallel indicator or buzzer |
Ambient Temperature | -10°C to +60°C |
Humidity | max. 95% |
Protection Class | IP 40 |
Weight | appr. 80 g |
Material | ABS |
Color | Housing white (similar to RAL 9003) |
Standards | EN 54-7, EN 54-17 |
Dimensions (H x D) | appr. 44 mm x 97 mm (with |
Response Sensitivity | Adjustable in 5 sensitivity levels |
DIN EN | 54-7, 54-17:2005 |
VdS-Approval | G 202002 |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the